The Data

As all the testing in this round up was performed with the exact same equipment, using the exact same methods I have decided to keep each radiators page uncluttered by posting our testing methodology, test set-ups and equipment used in a single location. To see exactly how the tests were carried out, details of the test set ups and equipment used, please head back to the RRU’15 Test Equipment Page.

Restriction Test

It’s generally agreed that radiators are one of, if not the least restrictive components in the water cooling loop. There are some exceptions however, so this must still be verified through testing:

sr1_5

Note: The picture above of the test set-up is for reference only, the SR-1 is not loaded so please disregard the readings.

Here is the raw data at the tested flow rates, displaying the measured Differential Pressure across the radiator as flow rate was increased.

sr1_6

The table numbers indicate that the SR-1 is a very low restriction radiator.  However numbers in isolation can only tell half the story. By plotting against other components it more easily shows the whole story. I have decided to use a HeatKiller 3.0 CPU block as the reference in these plots for two reasons. Firstly there is no chance of the plot being cluttered by curves overlapping and secondly it gives a reference point against a fairly common loop component of average restriction. For radiator to radiator restriction comparisons please see the RRU’15 data pages. As with all the radiator restriction plots I have limited the maximum flow rate displayed to 2.0 GPM as I suspect there are very few systems that operate above 2.0 GPM. For more information on how to read a restriction plot check out our guide.

SR1 - Restriction Chart

Now that we’ve seen how the SR1 performs vs flow, let’s take a few of those data points and compare to other radiators:

SR1 - Restriction Comparison 0.5

SR1 - Restriction Comparison 1.0

SR1 - Restriction Comparison 1.5

 

As can be seen the SR1 is a very low restriction radiator and there will be no problems connecting multiple of them in a loop.

Onwards to Thermal Performance!